Connect Sensors/Actuators - WAGO 765-4203/0100-0000 Product Manual

4-port io-link master class a; ethercat; 24 v dc; 2.0 a; 4 x m12 connection
Table of Contents

Advertisement

765-4203/0100-0000
Connection
®
Figure 9: Line Topology for EtherCAT
Networks (Module Image May Differ)

9.5 Connect Sensors/Actuators

The sensor/actuator cable provides power to the connected sensors/actuators and trans-
fers the sensor and actuator signals.
8 Design Power
Note the current load capacity of the supply contacts; see "Rule 3" in
Supply
[} 38], section Rule 3: Ports X01, X02 etc.
The following figure shows the potential routing of the two load circuits within the module.
If a port is operated in IO-Link mode, then at most 1 A can flow through pin 1 and pin 3
without additional measures. The use of standard cables allows lengths up to 20 m as
long as the current remains under 1 A.
Higher currents are possible and require a larger cable cross-section or shorter cable
length to keep the voltage drop for the outgoing and return paths below 1.2 V.
Product manual | Version: 1.0.0
59
4PORT IOL-A FLD EC DC 24V 2.0A

Advertisement

Table of Contents
loading

Table of Contents