Power Supply Concept; Design Power Supply - WAGO 765-4203/0100-0000 Product Manual

4-port io-link master class a; ethercat; 24 v dc; 2.0 a; 4 x m12 connection
Table of Contents

Advertisement

Planning

6.2 Power Supply Concept

6.2.1 Design Power Supply

NOTICE
!
Device damage if permissible current feedthrough exceeded
There is a risk of damage to the device and/or other devices connected to it if the maxi-
mum permissible current feedthrough is exceeded.
Power Supply of the Module and the Connected Sensors/Actuators
The 24 V power supply is fed in via the X31 (PWR IN) supply input. The module has two
electrically isolated supply cables.
• Supply cable 1 connects 1L+ (pin 1) to 1L- (pin 3).
• Supply cable 2 connects 2L+ (pin 4) to 2L- (pin 2).
The sensors or actuators are powered through ports X01, X02 etc. The design of the
power supply must take the demand of the connected sensors and actuators into ac-
count.
Successive devices can be powered through the X32 (PWR OUT) supply output. This
current feedthrough must also be taken into account in the design of the power supply.
Protective Functions
The module has integrated protective functions (see
prevent damage in overload situations such as overcurrent or short circuit. However, it is
important not to rely on these protective functions alone, but also to limit the currents ex-
ternally, because these protective functions do not cover the current feedthrough for pow-
ering successive devices through the supply output (X32). The maximum supply current
including the current feedthrough through X31 and X32 must be limited through fuse pro-
tection (see datasheet).
Consumption
For each supply cable, it is necessary to take into account the consumption that depends
on the connected devices.
Supply Cable 1:
• Logic supply (about 200 mA)
• Power supply of all connected sensors/actuators via 1L
• Power supply of successive devices via 1L
Supply Cable 2:
• Power supply of all connected sensors/actuators via 2L
• Power supply of successive devices via 2L
Rules
In addition to the consumption of the connected devices, rules for the maximum load ca-
pacity must be followed. Comply with the following rules to prevent damage to the prod-
uct:
• Supply voltage input X31 (PWR IN) and supply voltage input X32 (PWR OUT)