Derating; Regulations And Standards; Approvals; Table 18 Standards And Regulations - WAGO 765-4203/0100-0000 Product Manual

4-port io-link master class a; ethercat; 24 v dc; 2.0 a; 4 x m12 connection
Table of Contents

Advertisement

Properties

4.5 Derating

Please note the derating for use of the product. The surrounding air temperature and the
current affect the product's heat generation.
The derating curve was created with the following conditions of use: "without air move-
ment and with 0.5 m/s air movement" and "mounting on wall with poor heat conductivity."
The real conditions of use may lead to better heat dissipation from the product, e.g. due
to greater air movement or better dissipation of heat to the mounting wall. The product
provides measured values for temperature and current, which you can display with
WAGO Webserver I/O Field or read out via OPC UA.
The following figure shows the maximum permissible current (I) that can flow into the
product as a function of the surrounding air temperature (T).

4.6 Regulations and Standards

The following regulations and standards were used in the development of the module:
Standard
EN 61000-6-2
EN 61000-6-4
EN 61131-2
IEC 61158
IEC 60068-2-27 / 2008-02
IEC 60068-2-6 / 2007-12

4.7 Approvals

The following approvals have been granted for the product:
22
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
I
[A]
20
15
10
5
20
25
30
35
40
45
Title
Electromagnetic compatibility (EMC) – Immunity for industrial en-
vironments
Electromagnetic compatibility (EMC) – Emission standard for in-
dustrial environments
Programmable logic controllers
®
EtherCAT
Shock testing
Vibration testing (sinusoidal)
Conformity marking
UL
UL 61010-1 and UL
61010-2-201, "Ordinary
Location"
765-4203/0100-0000
0,5 m/s
0 m/s
T
[°C]
50
55
60
65
70
Figure 3: Derating, 0765-4203/0100-0000
Table 18: Standards and Regulations
In preparation.

Advertisement

Table of Contents
loading

Table of Contents