To do so, we consider port X01 of the 765-4203/0100-0000 module:
This has a load of 5.2 A = 2 A + 2 A + 0.5 A + 0.5 A + 0.2 A on pin 1. This exceeds the
maximum load capacity of 4 A and it thus not permitted.
If the currents on X01 and X02 of the 765-1701/0200-0000 IO-Link Hub were increased,
the overload protection would constantly activate and could threaten destruction of the
765-4203/0100-0000 IO-Link Master on its port X01.

6.3 Settings Options

6.3.1 Module Parameters

Indexes 0x2000 to 0x2003
Parameters with indexes 0x2000 to 0x2003 configure the module.
Index Subindex Parametername
0x2000.00
0x2001.00
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Figure 6: Power Supply Group with 765-4203/0100-0000 – Connection Example 2
Value Range
Force mode set-
0: Force mode enable
ting
1: Force mode disable
PD layout configu-
0: port-based
ration
1: pin-based
Table 39: Module Parameters
Default Description
0
The "Forcing" operating mode may be
used.
The "Forcing" operating mode must
not be used.
0
Order of the process data of the digi-
tal inputs and digital outputs:
Bit 0 = port X01 pin 4, bit 1 = port X01
pin 2,
bit 2 = port X02 pin 4, bit 3 = port X02
pin 2, ...
Order of the process data of the digi-
tal inputs and digital outputs:
Bit 0 = port X01 pin 4, Bit 1 = port X02
pin 4,
bit 2 = port X03 pin 4, bit 3 = port X04
pin 4,
...
bit 8 = port X01 pin 2, bit 9 = port X02
pin 2, ...