For entering these, there are two checkboxes in the table for each pin of a port: force for
switching the forcing functionality on/off, and set/clr for setting or deleting the setpoint
(1 bit); the latter checkbox is only relevant if the force box is checked. The following ap-
plies to this:
• All inputs for input simulation are entered in the right half of the table under "Input
process data"; all the inputs for output forcing are then entered in the left half of the ta-
ble under "Output process data."
You can find a description of and more information on the forcing function and explana-
tions of terms under
There is a separate table row for each of the 4 ports (X01...X04).
Concurrent Access
As long as one user is accessing the forcing functionality through a forcing medium, e.g.,
the WAGO I/O Field Webserver, it is locked for all other users of the module. They cannot
access the forcing functionality until the user that is active now terminates his or her ac-
cess.
In this case, the Web browser displays a message box with the text "Somebody else
is already forcing. Try again later." When the forcing functionality is being
accessed, a small orange icon also appears in the forcing option entry in the menu bar on
the left.

10.3.1.4.10 Forcing for IO-Link Ports

To access the forcing functionality for the IO-Link module via the Webserver, you must be
logged in there with operator or administrator rights. To perform forcing, proceed as fol-
lows:
Select the IOL Forcing option from the main menu of the Webserver on the left and
check the Forcing enable box at the top.
ð Unless another user is already accessing it, access to the forcing functionality is now
enabled. The screen shows a table with checkboxes in the force columns and should
look something like this:
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
8 Forcing
[} 29].