11.2.1.10 Events Triggered by the IO-Link Master

Events on the IO-Link master or its ports are reported by the IO-Link master to the Ether-
CAT slave, which forwards this to the EtherCAT master in the form of diagnostics.
The following values are set in the event qualifier:
TYPE = 2 (Warning) or 3 (Error)
MODE = 2 (Event disappears) or 3 (Event appears)
SOURCE = 1 (Master/local)
The following table lists the IO-Link event codes associated with IO-Link master events
and provides information on how to remedy faults.
IO-Link Event Code Description
0x17FF
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1809
0x180A
0x180B
0x180C
0x180D
0x180E
0x180F
0x1810
0x1811
0x1812
0x6000
108
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Alarm
Description
Forcing operat-
Forcing operating mode active (activated by
ing mode active
Web client or OPC UA client)
Short circuit on
Short circuit detected on pin 4
pin 4
Short circuit on
Short circuit detected on pin 2
pin 2
Short circuit on
Short circuit detected on pin 1.
pin 1
Process data error
No device access / loss of communi-
cation
Start parameter error
Incorrect device identification
Incorrect device identification
Short circuit on C/Q
PHY overtemperature
Short circuit on L+
Overcurrent on L+
Device event overflow
Backup inconsistency
Backup inconsistency
Backup inconsistency
Backup inconsistency
Parameter inconsistency
P24 (class B) missing or has under-
voltage
Short circuit on P24 (class B)
Short circuit on I/Q
Short circuit on C/Q
Overcurrent on I/Q
Invalid cycle time
765-4203/0100-0000
Remedy
The Web client or OPC UA
client should exit the Forcing op-
erating mode as soon as forcing
is no longer needed.
Eliminate short circuit.
Eliminate short circuit.
Eliminate short circuit.
Table 84: IO-Link Master Events
Remedy
Check submodule configuration
Check IO-Link port
Check parameters
Check port configuration parameters
Check port configuration parameters
Check wiring
Check temperature and load
Check wiring
Check power supply (e.g., 1L+)
Contact device manufacturer
Access outside the memory area (2048 octets)
Eliminate identity error
Unspecified error during data storage
Eliminate upload error
Eliminate download error
Check power supply
Check wiring (e.g., 2L+)
Check wiring
Check wiring
Check load
Check port configuration parameters