765-4203/0100-0000
Planning
• Power supply group via PWR OUT connection (with calculation of the permissible cur-
rent feedthrough)
• Power supply group with IO-Link hubs
These examples assume that the IO-Link inputs/outputs are configured as digital outputs.
Supply cable 1 then has a total current consumption of 2 × 2 A + 0.2 A = 4.2 A, and sup-
ply cable 2 has a total current consumption of 2 × 2 A = 4.0 A.
These do not exceed the maximum permissible value of 16 A per supply cable and are
thus permissible.
Example of a Power Supply Group via PWR OUT
If you connect another device to the PWR OUT (X32) power supply output, this forms a
supply group. The maximum permissible current feedthrough that this module can require
is 16 A – 4.2 A = 11.8 A for supply cable 1 (1L) und 16 A – 4.0 A = 12 A for supply ca-
ble 2 (2L).
Example of Individual Power Supply
This example considers a single 765-4203/0100-0000 module where no additional de-
vices are powered through its PWR OUT connection (X32).
Figure 4: Connection Example for 765-4203/0100-0000 Module with Individual Power Supply
One IO-Link class A device with max. current demand of 1 A is connected to each of
ports X01 through X04 of the module. The module's current consumption is 0.2 A.