Table 41 Io-Link Port Parameters - WAGO 765-4203/0100-0000 Product Manual

4-port io-link master class a; ethercat; 24 v dc; 2.0 a; 4 x m12 connection
Table of Contents

Advertisement

765-4203/0100-0000
Index Subindex Parametername
0x2100.03,
0x2110.03, ...
0x2100.04,
0x2110.04, ...
0x2100.05,
0x2110.05, ...
0x2100.24,
0x2110.24, ...
0x2100.24,
0x2110.24, ...
Indexes 0x8000 to 0x8070
Parameters with index 0x8000 configure port X01.
Parameters with index 0x8010 configure port X02.
Parameters with index 0x8020 configure port X03.
Parameters with index 0x8020 configure port X03.
Parameters with index 0x8070 configure port X04.
Index Subindex Parametername
0x8000.04,
0x8010.04,
...
0x8000.05,
0x8010.05,
...
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Value Range
Port X01/X02/...
0 (OFF)
1: On
DO Static on CQ
pin
Port X01/X02/...
0: Digital input NO Nor-
mally open
Digital mode IQ pin
1: Digital input NC Nor-
mally closed
2: digital output
3: static on
4: Not supported
Port X01/X02/...
0: No filter
Digital input filter
IQ pin
30: 3 ms filter time
150: 15 ms filter time
200: 20 ms filter time
Port X01/X02/...
0 ... 32
Configuration IOL
input length
Port X01/X02/...
0 ... 32
Configuration IOL
output length
Value Range
IO-Link port X01/
0, 1 ... 16777215
X02/...
Device ID
IO-Link port X01/
0, 1 ... 65535
X02/...
Vendor ID
Default Description
time the signal must be present in or-
der for a signal change to be de-
tected.
0
Pin 4 is a digital output.
Pin 4 is a digital output and switched
on (+24 VDC).
4
Pin 2 is a digital input. The input sig-
nal is not inverted.
Pin 2 is a digital input. The input sig-
nal is inverted.
Pin 2 is a digital output.
Pin 2 is a digital output and switched
on (+24 VDC).
Pin 2 is deactivated.
0
No filter active for detecting a signal
change of the pin 2 digital input sig-
nal.
Filter time setting for detecting a sig-
nal change of the pin 2 digital input
signal. The filter time is the amount of
time the signal must be present in or-
der for a signal change to be de-
tected.
0
Length of the input data
Set automatically by the configuration
software. Please do not change.
0
Length of the output data
Set automatically by the configuration
software. Please do not change.
Table 41: IO-Link Port Parameters
Default Description
0
Device ID
If validation is used: expected device
ID of the connected IO-Link device.
Device ID: see the documentation of
the IO-Link device used.
Value 0 if no validation is used.
0
Manufacturer ID
If validation is used: expected manu-
facturer ID of the connected IO-Link
device. Manufacturer ID: see the doc-
umentation of the IO-Link device
used.
Value 0 if no validation is used.
Planning
47