Figure 6-6: Default Idas Channels Setup - Teledyne 300E Instruction Manual

Carbon monoxide analyzer
Table of Contents

Advertisement

Model 300E Carbon Monoxide Analyzer
Instruction Manual
The Channel Properties. Triggering Events and Data Parameters/Functions for these
default channels are:
LIST OF DATA CHANNELS
These default Data Channels can be used as they are, or they can be customized
from the front panel to fit a specific application. They can also be deleted to make
room for custom user-programmed Data Channels.
P/N 04288 REV: A
Menu button sequence:
SETUP-DAS-EDIT-PASSWORD-ENTR
NAME: CONC
EVENT: ATIMER
REPORT PERIOD: 000:01:00
NUMBER OF RECORDS: 800
RS-232 REPORT: OFF
CHANNEL ENABLED: ON
CAL. HOLD OFF: ON
NAME: PNUMTC
EVENT: ATIMER
REPORT PERIOD: 000:01:00
NUMBER OF RECORDS: 360
RS-232 REPORT: OFF
CHANNEL ENABLED: ON
CAL. HOLD OFF: OFF
NAME: CALDAT
EVENT: SLPCHG
REPORT PERIOD: don't care
NUMBER OF RECORDS: 200
RS-232 REPORT: OFF
CHANNEL ENABLED: ON
CAL. HOLD OFF: OFF
Figure 6–6: Default iDAS Channels Setup
Operating Instructions
LIST OF PARAMETERS
Menu button sequence:
-EDIT-PARAMETERS-EDIT-YES
PARAMETER: O3CNC1
MODE: AVG
PRECISION: 1
STORE NUM.
SAMPLES: ON
PARAMETER: SMPFLW
MODE: AVG
PRECISION: 1
STORE NUM.
SAMPLES: OFF
PARAMETER: SMPPRS
MODE: AVG
PRECISION: 1
STORE NUM.
SAMPLES: ON
PARAMETER: SLOPE1
MODE: INST
PRECISION: 3
STORE NUM.
SAMPLES: OFF
PARAMETER: OFSET1
MODE: INST
PRECISION: 1
STORE NUM.
SAMPLES: OFF
PARAMETER: ZSCNC1
MODE: INST
PRECISION: 1
STORE NUM.
SAMPLES: OFF
109

Hide quick links:

Advertisement

Table of Contents
loading