Operation At Undervoltage; Alarm Detection At Undervoltage - Fuji Electric Faldic-a RYS-R Series User Manual

Ac servo system
Table of Contents

Advertisement

(12) System parameter 82, 83[Basic type, SX bus, T-link]
Para.
Name
82
Brake operation time
83
Brake releasing time
System para. 82 and 83 are the time setting of brake timing output.
If the external brake is used, setting change of system para. 81 is needed.
Brake operation time : Time period from when the motor shaft has been stopped, to when the P-action signal is on.
Brake releasing time : Time period from when manual forward or origin return command is on, to when the motor begins running.
(13) System parameter 84, 85[Basic type, SX bus, T-link]
Selects the operation when undervoltage at main circuit input is detected.
Para.
Name
84

Operation at undervoltage

85

Alarm detection at undervoltage

■ Operation at undervoltage (system para. 84)
Specifies the motor operation when undervoltage has been detected while the run command [RUN] is on.
Setting range
0: Rapid decel. to a stop
1: Free-run
■ Alarm detection at undervoltage (system para. 85)
Specifies the alarm detection operation when undervoltage has been detected while the run command [RUN] is on.
Setting range
0: No detection
1: Detects
If "0" has been set, the motor stops according to the preset operation to be made at undervoltage, and alarm detection will not be output.
Remark: If the power voltage decrease (undervoltage) due to momentary power failure is detected, the motor decelerates by system para.
84 setting. Due to regenerative power generated by the motor during deceleration, voltage level may exceed undervoltage level.
In this case, the motor starts deceleration at the undervoltage level. After that, the motor will accelerate again after alarm detection
of undervoltage is released.
Setting range
0.01 to 9.99 [s] (in 0.01 step)
0.01 to 9.99 [s] (in 0.01 step)
Setting range
0: Rapid deceleration to a stop
1: Free-run
0: No detection
1: Detects
Operation
The motor rapidly decelerates to a stop (within amplifier's highest capacity).
The motor decelerates (or accelerates) with free-run condition according to the load torque.
Operation
Alarm is not detected.
Undervoltage alarm is detected.
Initial value
0
1
6-41
Initial value
Change
0.50
Always
0.20
Always
Change
Power
Power
MHT260a (Engl.)