Ac Reactor; Ac Reactor Application; Suppression Of Higher Harmonics; Data Of External Braking Resistor - Fuji Electric Faldic-a RYS-R Series User Manual

Ac servo system
Table of Contents

Advertisement

10.5 AC reactor (reactor for impedance matching)

(1) AC reactor application

Provide and connect an AC reactor in any of the following cases.
(a) Power supply capacity is large
When the power supply capacity exceeds 500 [kVA] (*), the input current of the amplifier becomes large at the time of power on, and there is
a possibility where the rectifying diodes of the amplifier are damaged.
Note : (*) Cable length of 20 [m] with specified cable diameter size.
(b) Power supply voltage is unbalanced
Connect an AC reactor if the power supply voltage unbalance rate is 3% or higher.
Unbalance rate of power supply voltage [%] =
(c) Suppression of higher harmonics
Higher harmonics current is generated because an amplifier is of capacitor input type.
AC reactor suppresses voltage distortion in the power supply system.
(2) Connection
Connect an AC reactor to the primary (power supply) side of the amplifier.
Input voltage class
Amplifier output
Amplifier type
RYS□□□S3-

AC reactor

type
ACR2- 0.4A
reactance [mH] 2.92
10.6 External braking resistor : External dimension : Refer to 10.8 (3)
A braking resistor is provided (built-in) with the amplifier for 0.2 [kW] over.
However, if load variation is wide, elevation (hoisting) load, or higher frequent operation, the following external braking resistor should be
installed. In such a case, built-in resistor should be disconnected.

(1) Data of external braking resistor

Input voltage class
Amplifier output
Amplifier type
RYS□□□S3-
Resistor
type
(**)
Resistance
Built-in resistor
(**)
Note : (**) Cont. : Continuous operation duty at 25℃, allowable
(2) Data of NTC thermistor embedded in the external braking resistor
Resistor type
Open circuited the thermistor at
the following temperature [℃]
WSR-
401
135 ± 5
751
152
150 ± 10
DB
11-2
22-2
Max. voltage [V]−Min. voltage [V]
3-phase average voltage [V]
[V] 100
200
[kW] 0.05 to 0.2 0.03 to 0.2 0.4
□□□6
□□□
500 to 201 300 to 201 401
0.4A
[V]
100
[kW]
0.05, 0.1
0.2
□□□6
500, 101
201
WSR-401
[W] 17
[Ω] 68
[W]
Not
12
applicable
[Ω]
68
× 100
0.75
1, 1.5
751
102, 152
0.75A
1.5A
2.2A
1.57
0.939
0.679
200
0.03 to 0.2 0.4
0.75
□□□
300 to 201 401
751
WSR-751
25
15
Not
12
applicable
68
33
Withstand AC voltage tested
for one minute [kV]
1.5
2.5
10-6
2
3
4
202
302
402
3.7A
5.5A
7.5A
0.406
0.279
0.207
1, 1.5
2, 3
4, 5
102, 152
202, 302
402, 502
WSR-152
DB11-2
DB22-2
75
115
10
5.8
20
30
60
18
9
5.5
Contact capacity
30 [V] DC, 0.1 [A]
120 [V] AC/30 [V] DC, 0.1 [A]
MHT260a (Engl.)
5
502
11A
0.145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents