Compliance with EC directives

• This product should be installed in the electrical cabinet.
• Servo driver is used under the "pollution degree 2" environment as specified in IEC664.

(3) Peripheral equipment

(1)
(5)
(4)
(a) Power supply
The amplifier is used under the "over voltage category II" environment as specified in IEC 664.
The power input unit uses a reinforced isolation transformer based on IEC/EN standards.
A 3-phase, star-connected transformer should be used without regard to single-phase and 3-phase models. The transformer should be
grounded at the neutral point. The phase (line to earth) voltage must not exceed 120 [V].
(3)
(2)
For the interface power source, use a 24 [V] DC power source with reinforced isolation type input and output.
(b) Power filter
Regarding the EMI terminal disturbance voltage, a power filter is required.
Input voltage class
Amplifier output
Power filter type
HF□□□□A-TM
Current
Voltage
Leakage current
(7)
(6)
(1)
[V]
100
200
[kW]
0.05 to 0.2
0.03 to 0.4
3005
[A]
5
250[V] AC
1.5 [mA] max. at 250 [V] AC, 60 [Hz]
(2)
(8)
(9)
(1) Amplifier
(2) Reinforced isolation transformer
(3) 230 [V] / 3 = 133 [V]
0.75 to 1
1.5
3010
3015
10
15
3-7

(1) Power supply

source
(2) Amplifier
(3) Motor
(4) Control panel
(5) Reinforced
isolation
transformer
(3)
(6) Earth leakage
circuit breaker
(7) Auto circuit
breaker

(8) Power filter

(9) 24 [V] DC power
source
2
3
4
3020
3030
3040
20
30
40
MHT260a (Engl.)
5
3050
50