2: P
S
RODUCT
PECIFICATIONS
Relay Output Specifications
■ 24V DC Power Type
Type No.
No. of Outputs
Output Points per
Common Line
Terminal Arrangement
Output Type
Maximum Load Current
Minimum Switching Load
Initial Contact Resistance
Electrical Life
Mechanical Life
*1
Rated Load
Withstand Voltage
I/O Terminal Connector
*1 Values for resistive/inductive load.
Output Delay
ON
Input to Relay
OFF
ON
Output Relay Status
OFF
2-60
8
COM1
4
COM2
4
See "24V DC Power Type" on page 2-64.
1a contact
1
2 A maximum
*1
1 Common
7 A maximum
1.0 mA/5.0V DC (reference value)
30 mΩ or lower
100,000 operations minimum (rated load 1,800 operations/hour)
20,000,000 operations minimum (no load 18,000 operations/hour)
240V AC 2 A, 30V DC 2 A
Between Output
2,300V AC, 1 minute
Terminal and FE
Between Output
Terminal and
2,300V AC, 1 minute
Internal Circuit
Between Output
2,300V AC, 1 minute
Terminals (COMs)
Type
See "24V DC Power Type" on page 2-64.
Insertion/Removal
100 times minimum
Durability
FC6A S
MICROS
ERIES
FC6A-D16R1CEE, FC6A-D16R4CEE
OFF Bounce:
6 ms maximum
OFF Delay:
10 ms maximum
ON Bounce:
6 ms maximum
ON Delay:
6 ms maximum
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL

Hide quick links: