IDEC MICROSmart FC6A Series User Manual page 45

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

(4) Input Terminals
These terminals connect input devices such as push buttons and limit switches. DC inputs are both sinks and sources.
(5) Battery Holder
This holder is for installing the backup battery.
(6) Expansion Connector
This connector is used to connect expansion modules.
(7) Input LEDs [IN]
These LEDs turn on when an input is on. The LED with the corresponding number turns on.
(8) Output LEDs [OUT]
These LEDs turn on when an output is on. The LED with the corresponding number turns on.
(9) Power LED [PWR]
This LED turns on when the power is supplied to the CPU module.
(10) Run LED [RUN]
This LED turns on while the CPU module is running the user program.
This LED flashes when using certain functions while the user program is running.
LED
ON
Slow flashing (1 s cycle)
Quick flashing (100 ms cycle)
(11) Error LED [ERR]
This LED turns on when an error occurs in the CPU module.
(12) SD Memory Card Status LED [SD]
This LED turns on or flashes when the SD memory card is being read or written.
LED
OFF
ON
Slow flashing (1 s cycle)
Quick flashing (100 ms cycle)
(13) Battery Status LED [BAT]
This LED turns on or flashes when the remaining voltage in the backup battery is low.
LED
Off
Flashing (1 s cycle)
On
(14) Status LED [STAT]
This LED can be turned on or off in the user program.
(15) Output Terminals
These terminals connect output devices such as electromagnetic switches and solenoid valves. The CPU module is available
in the relay output type (240V AC: 2 A, 30V DC: 2 A), the transistor sink output type (0.5 A), and the transistor protection
source output type (0.5 A).
(16) CAN Port
This port allows J1939 communication.
(17) Ethernet Port 1
This port allows Ethernet communication with connected devices that are equipped with an Ethernet interface.
• While the CPU module is running the user program
• When executing the forced I/O function while the user program is running
• While the CPU module is in USB boot.
• When executing the forced I/O function while the user program is stopped
• When the SD memory card is not inserted
• When an unsupported or unformatted SD memory card was inserted
• Unmount SD memory card (M8072) is on, so the SD memory card has been unmounted
• When the FC6A Series MICROSmart power is off
• The standby state where the SD memory card can be written or read
• When the FC6A Series MICROSmart is recognizing the SD memory card
• Unmount SD memory card (M8072) is turned on and the FC6A Series MICROSmart is unmounting
the SD memory card (slow flashing, then off)
• Reading or writing the SD memory card
Condition
Battery voltage (D8056) > 2,300
2,300 ≥ battery voltage (D8056) > 2,000
2,000 ≥ battery voltage (D8056)
FC6A S
MICROS
ERIES
Status
Status
Normal
Warning
Dead battery
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
Battery Status
Sufficient battery level.
Low battery level. Replace the battery.
The battery is almost dead. Or no battery.
2-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents