Power Supply Specifications
■ AC Power Type
Type No.
Rated Operating Voltage
Voltage Fluctuation Range
Rated Power Frequency
Maximum Power Consumption
FC6A-C16R1AE
FC6A-C16R4AE
FC6A-C24R1AE
FC6A-C24R4AE
FC6A-C40R1AE
FC6A-C40R4AE
FC6A-C40R1AEJ
FC6A-C40R4AEJ
Allowable Momentary Power
Interruption
Withstand Voltage
Insulation Resistance
Inrush Current
Isolation
Ground
Grounding Wire
Power Supply Wire
Effect of Improper Power Supply
Connection
FC6A-C16R1AE
FC6A-C16R4AE
FC6A-C24R1AE
FC6A-C24R4AE
Weight
(approx.)
FC6A-C40R1AE
FC6A-C40R4AE
FC6A-C40R1AEJ
FC6A-C40R4AEJ
FC6A-C16R1AE, FC6A-C16R4AE, FC6A-C24R1AE,FC6A-C24R4AE, FC6A-C40R1AE,
FC6A-C40R4AE, FC6A-C40R1AEJ, FC6A-C40R4AEJ
100 to 240V AC
85 to 264V AC
50/60 Hz (47 to 63 Hz)
Standalone
33 VA
33 VA
35 VA
35 VA
41 VA
41 VA
37 VA
37 VA
10 ms or longer (when rated power supply voltage)
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Between power and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between relay output and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
40 A maximum
Between power terminal and internal circuit: Transformer isolated
D-type ground (Class 3 ground)
See "Recommended Ferrule List" on page 3-46
See "Recommended Ferrule List" on page 3-46
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
370 g
370 g
420 g
420 g
560 g
565 g
560 g
555 g
FC6A S
MICROS
U
ERIES
MART
When Maximum Load is Connected
54 VA
54 VA
61 VA
61 VA
74 VA
74 VA
74 VA
74 VA
'
M
FC9Y-B1722
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS