Input Internal Circuit
FC6-N08A11, FC6A-N08A14
470 kΩ
220 Ω
Input
150 nF
COM
Ambient Temperature, Input Voltage, Output Voltage, I/O Simultaneous ON Ratio
At conditions where the ambient temperature is 55°C and the input voltage is 132 V, the inputs can be 100% used.
When the FC6A Series MICROSmart is used in an ambient temperature of 55°C or higher, reduce the input voltage and I/O
utilization (simultaneous ON ratio: a%) according to the following diagrams. However, the following diagrams show the
temperature conditions when the FC6A Series MICROSmart is normally installed.
Note: Normally installed means the state in the diagram in "Normal Installation State" on page 3-1.
The usage conditions will also change according to the installation state. For details, see "Installation Location" on page 3-1.
FC6-N08A11, FC6A-N08A14
Input Voltage
132 V
120 V
102 V
Ambient
Temperature
65°C
0 V
0%
50%
2.21 kΩ
Ambient
Temperature 55°C
I/O
100%
Usage Limits