■ 12V DC Power Type
Type No.
Rated Input Voltage
Input Voltage Range
Rated Input Current
Terminal Arrangement
Input Impedance
Turn ON
Time
Input Delay
Time
Turn OFF
Time
Input Points
Isolation
Input Type
External Load for I/O Interconnection
Signal Determination Method
Effect of Improper Input Connection
Cable Length
Type
I/O Terminal
Connector
Insertion/Removal Durability
FC6A-C16R1DE
FC6A-C16R4DE
FC6A-C16K1DE
FC6A-C16K4DE
FC6A-C16P1DE
FC6A-C16P4DE
12V DC shared sink/source
0.0 to 18.0V DC
I0, I1, I6, I7
5 mA/point (at 12V DC)
I2 to I5, I10 to I27
6 mA/point (at 12V DC)
See "12V DC Power Type" on page 2-43
I0, I1, I6, I7
2.0 kΩ
I2 to I5, I10 to I27
2.0 kΩ
I0, I1, I6, I7
5 μs + software filter setting
I2 to I5
35 μs + software filter setting
I10 to I27
35 μs + software filter setting
I0, I1, I6, I7
5 μs + software filter setting
I2 to I5
35 μs + software filter setting
I10 to I27
100 μs + software filter setting
9 points in 1 common
line
Between Input
Not isolated
Terminals
Internal circuit
Photocoupler isolated
Type 1 (IEC61131-2)
Not needed
Static
Even if wiring for sink or source connection is incorrect, no damages are
caused.
However, if high voltage is applied that exceeds the input voltage range, there
is a risk of permanent damage.
3 m
See "12V DC Power Type" on page 2-43
100 times minimum
FC6A S
MICROS
ERIES
MART
FC6A-C40R1DE
FC6A-C40R4DE
FC6A-C40K1DE
FC6A-C40K4DE
FC6A-C40P1DE
FC6A-C40P4DE
24 points in 1 common line
U
'
M
FC9Y-B1722
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
FC6A-C40R1DEJ
FC6A-C40R4DEJ
FC6A-C40K1DEJ
FC6A-C40K4DEJ
FC6A-C40P1DEJ
FC6A-C40P4DEJ
2-23