Function Specifications
■ CPU Module Performance
Type No.
Program Data
Program
*1
Capacity
Comment Data
Basic Expansion
I/O Expansion
Expansion Interface
Cartridges
Basic
I/O Points
Basic Expansion
Expansion Interface
Cartridges
Expanded I/O with Expansion Interface
Remote Master/Slave Modules
User Program Download
Control System
Basic Instructions
Instructions
Advanced Instructions 124 type
Basic Instruction
Processing
Speed
END Processing
Internal Relay
Shift Register
Data Register
Counter (adding, reversible)
Timer (1 ms, 10 ms, 100 ms, 1 s)
*1 1 step is equivalent to 8 bytes.
*2 There are limitations on the maximum number of outputs that can be simultaneously turned on.
For details, see "Connection Restrictions When Expanding the PLC" on page 3-37.
*3 A maximum of three cartridges can be used by connecting the cartridge base module and HMI module.
*4 The maximum number of expansion modules that can be connected can be increased by using the expansion interface module. For details, see
"Expansion Interface Modules" on page 2-143.
Backup Function
Backup Data
Backup Battery
Battery Life
Replaceability
*1 D70000 to D269999 cannot be designated as "Keep." Data register values are kept when you switch the PLC from Stop to Run, but those values
are cleared at power up.
*2 To prepare for when the battery dies, the contents of RAM (internal relays, shift registers, counters, and data registers) can be saved to non-
volatile memory. For how to save the contents of RAM, see "SD Memory Card" on page 11-1.
*3 The battery is primarily consumed by backup current while unpowered. However, the ambient environment (temperature and humidity) while
unpowered and powered also affects consumption. In particular, battery life is greatly reduced in a high-temperature and high-humidity
environment, so replacement is recommended every year when the effect of the ambient environment (temperature and humidity) while
unpowered and powered is included.
*4 Replacement while powered and replacement while power is supplied from the USB bus are also possible. For the replacement method, see
"Replacing the Backup Battery" on page 3-34.
FC6A-D16R1CEE, FC6A-D16R4CEE
FC6A-D16K1CEE, FC6A-D16K4CEE
FC6A-D16P1CEE, FC6A-D16P4CEE
800,000 bytes
(100,000 steps)
384,000 bytes
7
8
*3
3
Input
8
Output
8
*2
224
*4
256
*3
12
I/O in the system can be expanded up to a maximum of 63 modules using expansion
interface modules (remote master/slave) (I/O points: maximum 2,016 points). For details,
see "Expansion Interface Modules (Remote Master/Slave)" on page 2-146.
1,000 times
Stored program system
42 type
0.021 ms/1,000 steps
1 ms
15,400
256
60,000
512
2,000
RAM (internal relays, shift registers, counters, data registers
Lithium ion primary cell (A battery is included with the product. The model of battery to be
included with the product cannot be specified.)
Panasonic: BR2032/CR2032A/CR2032B, Murata: CR2032X/CR2032W
Guaranteed 1 year, replacement recommended every 4 years (+25°C)
Replace within 1 minute after power off (recommended)
FC6A S
MICROS
ERIES
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
2: P
S
RODUCT
FC6A-D32K3CEE, FC6A-D32K4CEE
FC6A-D32P3CEE, FC6A-D32P4CEE
16
16
*1
*2
)
, clock
*3
*4
PECIFICATIONS