IDEC MICROSmart FC6A Series User Manual page 164

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

2: P
S
RODUCT
PECIFICATIONS
(3) Control Output LEDs [OUT0, OUT1]
On: Control output is on
Off: Control output is off
Flashing: For current output only, flashes at the duty cycle that corresponds to the output manipulated variable in a 100 ms
cycle.
For an output manipulated variable of 20%, the LED is on for 20 ms and off for 80 ms.
(4) Event Output LEDs [EVT0, EVT1]
On: When alarm 1 to alarm 8 or a loop error alarm has occurred
Off: When no alarms have occurred
(5) Auto Tuning/auto Reset LEDs [AT0, AT1]
Flashing: When executing auto tuning or auto reset
Off: When auto tuning or auto reset is stopped
(6) Manual Mode LEDs [MT0, MT1]
On: When program control mode is selected
Off: When auto mode is selected
(7) Fixed Value Control Mode/program Control Mode LEDs [F/P0, F/P1]
On: During program control mode
Off: During fixed value control mode
(8) Program Control Execution/hold LEDs [R/H0, R/H1]
On: During program control execution or while control is allowed in fixed value control
Flashing: When there is a power interruption during program control hold or during program control execution
Off: During program control stopped or while control prohibited in fixed value control
(9) External SP Enabled/disabled LEDs [R/L]
On: External SP input is enabled
Off: External SP input is disabled
(10) Terminal Name Label
Indicates terminal numbers.
(11) Cable terminals
These terminals are for connecting cables. Terminal block type (3.81 mm pitch).
(12) Expansion connector
Connects the expansion modules and the CPU module.
Model List
Module type
I/O Points
Non-contact
voltage output
(to drive SSRs)/
I/O
current
output type
Relay contact
I/O
output type
2-128
I/O Signal
Voltage input (0 to 10 V, 0 to 5 V, 1 to 5 V,
0 to 1 V)
Current input (4 to 20 mA, 0 to 20 mA)
2 (Input)
Thermocouple (K, J, R, S, B, E, T, N, PL-
II, C)
Resistance thermometer (Pt100, jPt100)
Voltage output (12V DC digital output)
2 (Output)
Current output (4 to 20 mA)
Voltage input (0 to 10 V, 0 to 5 V, 1 to 5 V,
0 to 1 V)
Current input (4 to 20 mA, 0 to 20 mA)
2 (Input)
Thermocouple (K, J, R, S, B, E, T, N, PL-
II, C)
Resistance thermometer (Pt100, jPt100)
2 (Output)
Relay output
FC6A S
MICROS
ERIES
Cable Terminal
Type 1
Terminal block type
(3.81 mm pitch)
Terminal block type
(3.81 mm pitch)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
Cable Terminal
Type No.
Type 2
Screw fastened type
FC6A-F2M1
Push-in type
FC6A-F2M4
Screw fastened type
FC6A-F2MR1
Push-in type
FC6A-F2MR4

Hide quick links: