3: I
NSTALLATION AND
Module Type
HMI module + cartridge
*1 Not included in the calculation of the connection restriction.
*2 There is no change in the current of the internal power supply for the cartridge base module, even if cartridges are connected.
*3 Current for the backlight. This is not included in the calculation of the connection restriction.
■ Connection Example 1
This example describes the number of connected modules, the internal 5 V line current, and the internal 24 V line current when
the expansion modules, HMI module, and cartridges in the below diagram are connected to the 16-I/O type.
No.
Module Type
(1)
HMI Module (no installed cartridges)
(2)
Communication Cartridge
(3)
Digital Output Module
(4)
Digital Input Module
(5)
Analog Input Module
(6)
Analog Input Module
Number of connected modules
For the 16-I/O type, the number of modules that can be connected must be four expansion modules (basic expansion side),
one HMI module, and two cartridges or lower. There are four expansion modules (basic expansion side), one HMI module,
and one cartridge, so there is no problem because the maximum number of modules was not exceeded.
Internal 5 V line current
The current must be 695 mA or lower. The total current is 415 mA, so there is no problem because it is not exceeded 695 mA.
Internal 24 V line current
The current must be 126 mA or lower. The total current is 48 mA, so there is no problem because it is not exceeded 126 mA.
3-40
W
IRING
FC6A-PH1+FC6A-PJ2A
FC6A-PH1+FC6A-PJ2CP
FC6A-PH1+FC6A-PK2AV
FC6A-PH1+FC6A-PK2AW
FC6A-PH1+FC6A-PC1
FC6A-PH1+FC6A-PC3
FC6A-PH1+FC6A-PC4
FC6A-PH1+FC6A-PN4
FC6A-PH1+FC6A-PTK4
FC6A-PH1+FC6A-PTS4
FC6A
FC6A-PH1
-C16P1CE
(1)
FC6A-PC3
FC6A-PH1
FC6A-PC3
FC6A-T32P3
FC6A-N32B3
FC6A-J4CN1
FC6A-J4A1
FC6A S
MICROS
ERIES
Model
FC6A-T32P3
FC6A-J4CN1
FC6A-N32B3
(2)
(3)
(4) (5) (6)
Model
Internal 5 V Line Current
415 mA (695 mA or lower)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
Internal 3.3 V
Internal 5 V
*1
Line Current
Line Current
―
170 mA
―
170 mA
―
250 mA
―
360 mA
―
180 mA
―
230 mA
―
290 mA
―
175 mA
―
175 mA
―
175 mA
FC6A-J4A1
Internal 24 V Line Current
150 mA
60 mA
45 mA
48 mA (= 1.5 mA × 32 points)
65 mA
50 mA
45 mA
48 mA (126 mA or lower)
Internal 24 V
Line Current
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
*3
15 mA
―
―
―
―
―