Digital Input Specifications
Type No.
Rated Input Voltage
Operating Load Voltage Range
Rated Input Current
Terminal Arrangement
Input Impedance
Turn ON Time
Input Delay Time
(24V DC)
Turn OFF Time
External Load for I/O
Interconnection
Signal Determination Method
Effect of Improper Input Connection
Cable Length
Input Operating Range
The operating range of Type 1 (IEC 61131-2) DC input modules is as follows.
Input Voltage (V DC)
28.8 V
24 V
ON Area
8.5 V
Transition Area
5 V
OFF Area
0.9 mA
1.7 mA
Input Internal Circuit
4.3 kΩ
Input
COM
12/24V DC (shared sink/source)
0 to 28.8V DC
5 mA/1 point (when 24V DC)
2.5 mA/1 point (when 12V DC)
See "Wiring Arrangement and Wiring Examples" on page 2-167.
4.4 kΩ
0.5 ms
0.5 ms
Not needed
Static
Even if wiring for sink or source connection is incorrect, no damages are caused.
If any input exceeding the rated value is applied, permanent damage may be caused.
3 m
Input Current (mA)
6.4 mA
5.3 mA