IDEC MICROSmart FC6A Series User Manual page 305

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

Click the Stop button to stop operation, then the start control special internal relay M8000 is turned off.
5.
The PLC operation can also be started and stopped while WindLDR is in the monitor mode. Select Online > Monitor >
Monitor and click the Start or Stop button.
Note: Special internal relay M8000 is a keep type internal relay and stores the status when the power is turned off. M8000 retains its previous status
when the power is turned on again. However, when the backup battery is dead, M8000 loses the stored status, and can be turned on or off as
programmed when the FC6A Series MICROSmart is powered up. The selection is made in Configuration > Run/Stop Control > Run/Stop
Selection at Memory Backup Error. See "Run/Stop Selection at Keep Data Error" on page 5-9.
Start/Stop Operation Using the Power Supply
The FC6A Series MICROSmart can be started and stopped by turning power on and off.
Power up the FC6A Series MICROSmart to start operation.
1.
Turn power on and off to start and stop operation.
2.
FC6A S
MICROS
U
ERIES
MART
'
M
FC9Y-B1722
SER
S
ANUAL
4: O
B
PERATION
ASICS
4-19