IDEC MICROSmart FC6A Series User Manual page 89

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

Power Supply Specifications
■ 24V DC Power Type
Type No.
Rated Power Voltage
Voltage Fluctuation Range
Maximum Power Consumption
FC6A-D16R1CEE/
FC6A-D16R4CEE
FC6A-D16K1CEE/
FC6A-D16K4CEE
FC6A-D16P1CEE/
FC6A-D16P4CEE
FC6A-D32K3CEE/
FC6A-D32K4CEE
FC6A-D32P3CEE/
FC6A-D32P4CEE
Allowable Momentary Power
Interruption
Withstand Voltage
Insulation Resistance
Inrush Current
Isolation
Ground
Grounding Wire
Power Supply Wire
Effect of Improper Power Supply
Connection
FC6A-D16R1CEE, FC6A-D16R4CEE, FC6A-D16K1CEE, FC6A-D16K4CEE, FC6A-D16P1CEE,
FC6A-D16P4CEE, FC6A-D32K3CEE, FC6A-D32K4CEE, FC6A-D32P3CEE, FC6A-D32P4CEE
24V DC
20.4 to 28.8V DC (including ripple)
Standalone
2.88 W (24V DC)
2.88 W (24V DC)
2.88 W (24V DC)
3.36 W (24V DC)
3.36 W (24V DC)
10 ms or longer (when rated power supply voltage)
Between power and FE terminals: 500V AC, 1 minute
Between input and FE terminals: 500V AC, 1 minute
Between transistor output and FE terminals: 500V AC, 1 minute
Between relay output and FE terminals: 2,300V AC, 1 minute
Between power and input terminals: 500V AC, 1 minute
Between power and transistor output terminals: 500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and transistor output terminals: 500V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Between power and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between transistor output and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between relay output and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and transistor output terminals: 100 MΩ or higher (500V DC insulation resistance
tester)
Between power and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and transistor output terminals: 100 MΩ or higher (500V DC insulation resistance
tester)
Between input and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
35 A maximum
Between power terminal and internal circuit: Transformer isolated
D-type ground (Class 3 ground)
See "Recommended Ferrule List" on page 3-46.
See "Recommended Ferrule List" on page 3-46.
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
FC6A S
MICROS
ERIES
MART
When Maximum Load is Connected
18.24 W (24V DC)
18.24 W (24V DC)
18.24 W (24V DC)
18.72 W (24V DC)
18.72 W (24V DC)
U
'
M
FC9Y-B1722
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
2-53