Forced I/O Function

Inputs can be forced on/off regardless of the status of physical inputs, and outputs can be forced on/off regardless of the ladder
logic using the forced I/O function in WindLDR. The force input function can be used to monitor or online edit mode to test the
ladder logic without the need of wiring the input terminals or turning on the actual inputs. The force output function can be used
to turn on/off the outputs to the external devices.
The forced I/O may cause unexpected operation of the FC6A Series MICROSmart. Make sure of safety before forcing inputs
Caution
or outputs.
Devices
All the inputs and outputs of the FC6A Series MICROSmart can be forced on/off individually.
All-in-One CPU module
Type
16-I/O type
I0 to I10, I30 to I627, I630 to I633
24-I/O type
I0 to I15, I30 to I627, I630 to I633
40-I/O type
I0 to I27, I30 to I627, I630 to I637
Plus CPU module
Type
I0 to I7, I30 to I627, I630 to I643,
I1000 to I1597, I2000 to I2597, I3000 to I3597,
Plus 16-I/O type
I4000 to I4597, I5000 to I5597, I6000 to I6597,
I7000 to I7597, I8000 to I8597, I9000 to I9597,
I10000 to I10597
I0 to I17, I30 to I627, I630 to I643,
I1000 to I1597, I2000 to I2597, I3000 to I3597,
Plus 32-I/O type
I4000 to I4597, I5000 to I5597, I6000 to I6597,
I7000 to I7597, I8000 to I8597, I9000 to I9597,
I10000 to I10597
Forced I/O Status
Events of the FC6A Series MICROSmart and effects on the forced I/O settings are shown below.
When the FC6A Series MICROSmart starts running
When the FC6A Series MICROSmart is stopped.
When the FC6A Series MICROSmart is powered up
When user program download is executed
When Reset Input is turned on
When Clear All Devices is executed in the PLC Status dialog
box of WindLDR
When the system software download is executed
Note: Force function has no effect on high-speed counters, catch inputs, or interrupt inputs. The stop or reset input can be initiated using the force
function, but the force settings will be cleared as soon as the reset input is turned on.
Checking Forced I/O Function Execution State
The forced I/O function status (running or stopped) can be checked with WindLDR or with the FC6A Series MICROSmart run LED [RUN].
Details on the run LED [RUN] that shows the forced I/O function status are as follows.
LED
ON
Slow flashing (1 s cycle)
Quick flashing (100 ms cycle)
5-50
Inputs
Inputs
Events
When the forced I/O function is stopped while the CPU module is running the user program
When executing the forced I/O function while the user program is running
When executing the forced I/O function while the user program is stopped
FC6A S
MICROS
ERIES
Device Range
Q0 to Q6, Q30 to Q627, Q630 to Q633
Q0 to Q11, Q30 to Q627, Q630 to Q633
Q0 to Q617, Q30 to Q627, Q630 to Q637
Device Range
Q0 to Q7, Q30 to Q627, Q630 to Q643,
Q1000 to Q1597, Q2000 to Q2597, Q3000 to Q3597,
Q4000 to Q4597, Q5000 to Q5597, Q6000 to Q6597,
Q7000 to Q7597, Q8000 to Q8597, Q9000 to Q9597,
Q10000 to Q10597
Q0 to Q17, Q30 to Q627, Q630 to Q643,
Q1000 to Q1597, Q2000 to Q2597, Q3000 to Q3597,
Q4000 to Q4597, Q5000 to Q5597, Q6000 to Q6597,
Q7000 to Q7597, Q8000 to Q8597, Q9000 to Q9597,
Q10000 to Q10597
The force settings are retained. The forced inputs and outputs are kept on/off
even after the FC6A Series MICROSmart is stopped, regardless of the status
of M8025 (maintain outputs while FC6A Series MICROSmart is stopped).
The force settings are retained, but the force is suspended. If the battery is
dead, the force settings are cleared.
The force settings are retained, and whether the force will be suspended or
not can be selected in the Download Program dialog box.
The force settings are cleared.
Status
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
Outputs
Outputs
Forced I/O Status