Input/Output Wiring - IDEC MICROSmart FC6A Series User Manual

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

3: I
NSTALLATION AND

Input/Output Wiring

This section describes FC6A Series MICROSmart input/output device wiring.
Precautions for I/O Device Wiring
Input Terminal Wiring
When wiring input devices, separate wiring from power, output, and motor lines.
For the wires to use with the CPU modules, expansion modules, and cartridges, see "Recommended Ferrule List" on page 3-46.
DC Sink Input Wiring Example
+
2-wire
Sensor
PNP
+
12/24V DC
*1
-
*1 24V DC for products with a version number lower than V400. For details on the version number of modules, see "Checking the Version Number"
on page 2-1.
Output Terminal Wiring
If output relays or transistors in the FC6A Series MICROSmart or output modules should fail, outputs may remain on or
Caution
off. For output signals which may cause heavy accidents, provide a monitor circuit outside the FC6A Series MICROSmart.
Connect a fuse to the output module, selecting a fuse appropriate for the load.
When equipment containing the FC6A Series MICROSmart is intended for use in European countries, insert an IEC 60127-
approved fuse to each output of every module for protection against overload or short-circuit. This is required when
equipment containing the FC6A Series MICROSmart is destined for Europe.
When driving an inductive load that emits noise like a magnet or a valve, to reduce noise and protect circuits, use a diode
for the output on DC power type models and a surge absorber for the output on AC power type models.
For the wires to use with the CPU modules, expansion modules, and cartridges, see "Recommended Ferrule List" on page
3-46.
3-18
W
IRING
DC.IN
0
1
2
3
4
5
6
7
-
FC6A-N08B1
FC6A S
MICROS
ERIES
DC Source Input Wiring Example
-
2-wire
Sensor
-
12/24V DC
*1
+
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
DC.IN
0
1
2
3
4
5
6
7
+
NPN
FC6A-N08B1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents