2: P
S
RODUCT
PECIFICATIONS
Wiring Arrangement and Wiring Examples
Caution
FC6A-PK2AV
OUT0
+
NC
+
0 to 10 V
Analog Voltage Input Device
FC6A-PJ2A
IN0
+
+
+
0 to 10 V
Analog Voltage Output Device
2-172
Do not connect a thermocouple to a part with hazardous voltage (60V DC or peak 42.4V DC or higher part).
Before turning on the power, please check that the wiring is correct. If the wiring is incorrect, the analog I/O cartridge
may be damaged. When the analog I/O cartridge may malfunction due to noise, wire it with a shielded cable and
connect both ends to the FE.
When connecting cables to the analog I/O cartridges, the tightening torque is 0.22 to 0.25 Nm.
OUT1
+
NC
+
0 to 10 V
Analog Voltage Input Device
IN1
+
+
0 to 20 mA
4 to 20 mA
Analog Current Output Device
FC6A S
MICROS
ERIES
FC6A-PK2AW
OUT0
NC
4 to 20 mA
Analog Current Input Device
FC6A-PJ2CP
IN0
A
B
+
+
A
B
Pt / Ni
Resistance Thermometer
U
'
M
MART
SER
S
ANUAL
+
NC
+
Analog Current Input Device
B'
A
NC
+
B'
+
Thermocouple
FC9Y-B1722
OUT1
+
+
4 to 20 mA
IN1
B
B'
NC