IDEC MICROSmart FC6A Series User Manual page 596

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

11: SD M
C
EMORY
ARD
Downloading and Uploading Device Address Data
Device Address Data
Device Address Data Format
The device address data consists of group of values. The number of values is specified with Number of Data in Device Address
Data Setting dialog box.
"(Value of device address)",
"(Value of device address number + 1)",
"(Value of device address number + 2)",
.
.
.
"(Value of device address number + (
Creating Device Address Data with Text Editor
The device address data can be created with software tool such as Notepad, text editor from the third party, or spread sheet
software.
1.
Describe "Device Address Value", comma (,), and line feed as many as the number of data.
Example: When the number of data is 5 and values are 1111, 2222, 3333, 4444, 5555 in this order
1111,
2222,
3333,
4444,
5555,
Save the file with the extension (.csv).
2.
Supported Device Address
The range of device addresses that can be read or written and the maximum number of data are as follows.
Device Name
Internal relay
Special internal relay
Shift register
Timer preset value
Counter preset value
Data register
Special data register
Non-retentive data
register
11-60
n
-1))",
FC6A-C16/-C24/-C40/-C40XEJ
Device Address
Max Number of Data
M0 to M7997
M10000 to M17497
M8000 to M8317
R0 to R255
TP0 to TP1023
CP0 to CP511
D0 to D7999
D10000 to D55999
D8000 to D8499
-
FC6A S
MICROS
ERIES
Number of data (
n
)
Device Address
6,400
M0 to M7997
6,000
M10000 to M21247
256
M8000 to M9997
256
R0 to R255
1,024
TP0 to TP1999
512
CP0 to CP511
8,000
D0 to D7999
46,000
D10000 to D61999
500
D8000 to D8899
-
D70000 to D269999
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
FC6A-D16/-D32
Max Number of Data
6,400
9,000
1,600
256
2,000
512
8,000
52,000
900
200,000

Hide quick links:

Advertisement

Table of Contents
loading