IDEC MICROSmart FC6A Series User Manual page 549

Windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

When the trigger devices are simultaneously turned on for multiple recipe blocks
Processing is executed in order from the lowest recipe block number. However, if a new trigger device is turned on for the recipe block
being executed, it will be executed as the new recipe block after reading or writing of the recipe block being executed has finished.
Block
Scan
Number
1
1st scan
30
1
2nd scan
30
1
3rd scan
30
1
4th scan
30
1
5th scan
30
Used Special Devices
The special internal relays and the special data registers used by the recipe function are as follows.
Special Internal Relays
Device Address
Function
M8260
Write Recipe Execution Flag
M8261
Read Recipe Execution Flag
M8262
Executing Write Recipe
M8263
Executing Read Recipe
Recipe Channel Execution
M8264
Completed Output
Recipe Execution Error
M8265
Output
Recipe Block Execution
M8266
Completed Output
Read Restriction for
M8267
Recipe Internal Memory
(ROM-Range)
Special Data Registers
Device Address
Function
D8260
Recipe Block Number
Recipe Execution Block
D8261
Number
Recipe Execution Channel
D8262
No.
Recipe Execution
D8263
Operation
D8264
Recipe Execution Status
Recipe Execution Error
D8265
Information
Recipe Internal Memory
D8266
(ROM-Range 1) Read
Count
Recipe Internal Memory
D8267
(ROM-Range 2) Read
Count
Trigger Device
Channel 1
Channel 8
OFF
OFF
OFF
OFF
OFF -> ON
OFF
OFF -> ON
OFF
ON
OFF -> ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
When M8260 is turned on, write recipe is executed.
When M8261 is turned on, read recipe is executed.
M8262 is turned on when the write recipe processing starts, and it is turned off when the
processing has completed. M8262 also is turned off when read recipe processing starts.
M8263 is turned on when the read recipe processing starts, and it is turned off when the
processing has completed. M8263 also is turned off when write recipe processing starts.
M8264 is turned off when starting to read or write a recipe channel, and it is turned on when
reading or writing a recipe channel has completed.
M8265 is turned on when recipe execution has completed and D8264 (Recipe Execution Status)
is a value other than 0.
M8266 is turned off when starting to read or write a recipe block, and it is turned on when
reading or writing a recipe block has completed.
M8267 is turned on when reading or writing to a recipe block in internal memory (ROM-Range)
has completed. When M8267 is on, recipes cannot be read to internal memory (ROM-Range).
When M8267 is off, recipes can be read to internal memory (ROM-Range).
The recipe block number to read or write using special internal relays.
All channels for the specified block number are applicable.
The recipe block number of the recipe that was executed.
This is updated when the recipe block starts, and the status is retained when completed.
The channel number of the recipe that was executed.
This is updated when the channel processing starts, and the status is retained when completed.
Information about the operation of the recipe that was executed. For details, see "Recipe
Execution Operation (D8263)" on page 11-14.
The status of the recipe that was executed. This is 0 when normally terminated. For details, see "Recipe
Execution Status (D8264) and Recipe Execution Error Information (D8265)" on page 11-14.
M8264 turns on when this device is updated. M8265 also turns on if this device is a value other than 0.
Error information about the recipe that was executed. This device is updated at the same time as
D8264. For details, see "Recipe Execution Status (D8264) and Recipe Execution Error Information
(D8265)" on page 11-14.
The number of times device values are read to internal memory (ROM-Range 1) as recipe data is
stored in this register in units of 100. An error occurs when the actual read count exceeds 50,000
times (value of D8266 > 500).
The number of times device values are read to internal memory (ROM-Range 2) as recipe data is
stored in this register in units of 100. An error occurs when the actual read count exceeds 50,000
times (value of D8267 > 500).
FC6A S
MICROS
ERIES
MART
Channel 15
OFF
No operation
OFF
OFF -> ON
Execute channel 1 in block 1
OFF
ON
Execute channel 15 in block 1
OFF
ON
Execute channel 1 in block 30
OFF
ON
Execute channel 8 in block 1
OFF
Description
Description
U
'
M
FC9Y-B1722
SER
S
ANUAL
11: SD M
EMORY
Recipe Execution Status
C
ARD
11-13