Selection and protection of a motor
4.9.3
To exhibit the best performance of the motor performance (offline auto tuning)
(Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859)
The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
When performing Advanced magnetic flux vector control or General-purpose magnetic flux vector control, the motor
can be run with the optimum operating characteristics by automatically measuring the motor constants (offline auto
tuning) even when each motor constants differs, other manufacturer's motor is used, or the wiring length is long.
Parameter
Name
Number
71
Applied motor
80
Motor capacity
81
Number of motor poles
82
Motor excitation current
83
Rated motor voltage
84
Rated motor frequency
90
Motor constant (R1)
91
Motor constant (R2)
92
Motor constant (L1)
93
Motor constant (L2)
94
Motor constant (X)
Auto tuning setting/
96
status
859
Torque current
The above parameters can be set when Pr. 160 User group read selection = "0".(Refer to page 179)
112
Initial Value
Setting Range
0, 1, 3 to 6,
0
13 to 16, 23, 24, 40,
43, 44, 50, 53, 54
0.1 to 15kW
9999
2, 4, 6, 8, 10
9999
0 to 500A
9999
200V class
200V
0 to 1000V
400V class
400V
50Hz
10 to 120Hz
9999
0 to 50Ω, 9999
9999
0 to 50Ω, 9999
9999
0 to 1000mH, 9999
9999
0 to 1000mH, 9999
9999
0 to 100%, 9999
0
0 to 500A
9999
By selecting a standard motor or constant-
torque motor, thermal characteristic and motor
constants of each motor are set.
Applied motor capacity.
9999
V/F control
Number of motor poles.
9999
V/F control
Tuning data
(The value measured by offline auto tuning is
automatically set.)
Uses the Mitsubishi motor (SF-JR, SF-HR,
9999
SF-JRCA, SF-HRCA) constants.
Rated motor voltage (V).
Rated motor frequency (Hz).
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999: Uses the Mitsubishi motor (SF-JR, SF-
HR, SF-JRCA, SF-HRCA) constants.
0
Offline auto tuning is not performed
For Advanced magnetic flux vector control
1
Offline auto tuning is performed without motor
running (all motor constants).
For General-purpose magnetic flux vector
control
11
Offline auto tuning is performed without motor
running.
(motor constant (R1) only)
Offline auto tuning for V/F control (automatic
21
restart after instantaneous power failure (with
frequency search)) (Refer to page 156)
Tuning data
(The value measured by offline auto tuning is
automatically set.)
Uses the Mitsubishi motor (SF-JR, SF-HR,
9999
SF-JRCA, SF-HRCA) constants.
Description