6.3.5 Setting the WARNING value for the water flow
PRG.
SET POINT
ENTER
WATER WARNING?
PRG.
SET POINT
WATER FLOW LOW?
▲
▼
SET POINT
WATER FLOW DLY?
▼
"▲" "▼" Use the up down arrow keys to change the setting value.
Set Water Flow
"▲" : Increase the setting value by 0.1 L/min
"▼" : Decrease the setting value by 0.1 L/min
Upper limit : 19.0 L/min
Lower limit : 3.0 L/min
Factory setting : 3.0 L/min
Set Water Dly
"▲" : Increase the setting value by 1 sec
"▼" : Decrease the setting value by 1 sec
Upper limit : 60sec
Lower limit : 5 sec
Factory setting : 60sec
WATER FLOW LOW
ENTER
##.# L/min
WATER FLOW DLY
ENTER
## SEC
Setting
ENTER
Completed
Setting
ENTER
Completed