Tripper Switch Setting; Application Assistance - Siemens airanger DPL PLUS Instruction Manual

Table of Contents

Advertisement

Parameter Settings for Point # 1
Number
P001
Operation
P002
Material
P003
Measurement Response
P004
Transducer
P005
Units
P006
Empty
P007
Span
P070
Failsafe Timer
P200
mA Range
P219
mA Failsafe

Tripper Switch Setting

Before RUN mode entry, set the AiRanger DPL Plus Tripper switch (immediately above
the mA output terminals) in the TRIP position, rather than the NORM position.
With the PLC disabled, enter the RUN mode (or perform a Reading Simulation, P920).
When satisfied with system performance and programming, connect mA Output 1 to the
PLC.
The Reading displayed when the tripper car is at the near stop is 0.00 ft and 275 ft at the
far end stop (distance from the Span (P007) reference point).
Note that (if used) Relay Setpoints (P112/P113) and mA Setpoints (P210/P211) are
referenced to the Transducer 1 face when the tripper car is at the far end stop. (Enter
setpoint values based on the tripper car travel from far.)
For a completely automated Tripper Car system, position the Tripper Car via the PLC,
based upon bunker material level, as monitored by a separate level measurement system
(e.g. Siemens Milltronics AiRanger XPL Plus).

Application Assistance

The preceding examples describe only a few ways in which the AiRanger DPL Plus can
be applied to process measurement requirements.
The AiRanger DPL Plus can be used to monitor almost any process (within the
temperature, measurement range, and chemical immunity capabilities of the system)
where a distance measurement or determination of presence vs. lack of presence of an
object is desired.
Page 108
Description
AiRanger DPL Plus – INSTRUCTION MANUAL
Instructions
Enter "8" for tripper.
Enter "1" (Use flat surface for Tripper Operation.)
No entry required (preset to "2" for medium response,
1 m/min).
Enter "110" for XLS-60 Transducers.
Enter "4" for feet.
Enter "325" for 325 foot face to face distance (tripper at
far stop).
Enter "275" for 275.0 ft travel to near stop.
Enter "2" for 2 minutes (14 ft at the maximum travel
rate).
No entry required (preset to space, near = 4 ma; far =
20 mA).
Enter "3.8" for 3.8 mA output on "LOE".