Cabinet design and EMC for components, Blocksize format
10.8 Information on control cabinet cooling
10.8.3.3
Power loss for line reactors and line filters
Table 10- 21 Overview of power loss during rated operation for line reactors and line filters
Rated output current I
rated
Line reactors for Power Modules blocksize
4.0 A
11.3 A
22.3 A
47.0 A
Line reactors for Chassis Power Modules
210 A
260 A
310 A
380 A
490 A
Line filter for Power Modules blocksize
15 A
23.5 A
49.4 A
Line filters for Chassis Power Modules
210 A/260 A
310 A/380 A
490 A
10.8.3.4
Power loss for Power Modules
Table 10- 22 Overview of power loss during rated operation for Power Modules
Rated output current I
rated
based on I
rated
PM240-2 Blocksize
7.5 A/0.55 kW
9.6 A/0.75 kW
13.5 A/1.1 kW
18.1 A/1.5 kW
24.0 A/2.2 kW
35.9 A/3.0 kW
43.0 A/4.0 kW
29.0 A/5.5 kW
37.0 A/7.5 kW
44.0 A/11 kW
56.0 A/15 kW
380
Frame size
FSA (1.1 kW)
FSA (4.0 kW)
FSB
FSC
FX
FX
GX
GX
GX
FSA
FSB
FSC
FX
GX
GX
/Unit rating
Frame size
FSA
FSA
FSB
FSB
FSB
FSC
FSC
FSC
FSC
FSD
FSD
Line voltage
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
Line voltage
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
1 AC/3 AC 200 ... 240 V
3-phase 200 ... 240 VAC
3-phase 200 ... 240 VAC
3 AC 200 ... 240 V
3 AC 200 ... 240 V
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Unit
Power loss
50/60 Hz
W
23/25.3
W
36/39.6
W
53/58.3
W
88/96.8
W
274
W
247
W
267
W
365
W
365
W
13
W
22
W
39
W
49
W
49
W
55
Unit
Power loss
kW
0.04
kW
0.04
kW
0.05
kW
0.07
kW
0.12
kW
0.14
kW
0.18
kW
0.20
kW
0.26
kW
0.42
kW
0.57
AC Drive