Technical Data

Voltage input
Input voltage
Input power
Protection type
Rated impulse voltage
Voltage outputs
Output voltage 1 (internal)
Output voltage 2 (internal)
Output voltage 3 (external)
Output voltage for contact wetting
Output power 1
Output power 2
Output power 3
Guaranteed interruption time
Mechanics
Connections
1)
not short-circuit proof and not overload proof
2)
protective mechanism is a self resetting fuse (PTC)
statistical values:
90
Unrestricted
DC 24...60 V
*)
caused by the connection between input voltage and AUXV0
the input voltage must be < DC 70 V
**)
the reliable function of the power supply is guaranteed up to
DC 78 V
34 W
Double insulation
4 kV
DC 5.2 V ±3%
DC 12 V +30/-5%
DC 5.2 V
1)
±3%
Equals input voltage
2.5 W
3 W
5 W
100 ms
Removable screw terminals for direct conductor assembly
cross-section up to 2.5 mm²
operation voltage: DC 60 V max.
switching capacity: < 40 A
ohmic resistance: < 5 Ω
permanent floating current after activation of the fuse: < 1.3 A
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
*)
+15%/-25%
**)
+30%/-25%
3x each 100 mA
DC8-037-2.02, Edition 10.2017