Parameter Description
8-43 PCD Read Configuration
Range:
[1660]
Digital Input
[1661]
Terminal 53 Switch Setting
[1662]
Analog Input 53
[1663]
Terminal 54 Switch Setting
[1664]
Analog Input 54
[1665]
Analog Output 42 [mA]
[1666]
Digital Output [bin]
[1667]
Pulse Input #29 [Hz]
[1668]
Pulse Input #33 [Hz]
[1669]
Pulse Output #27 [Hz]
[1670]
Pulse Output #29 [Hz]
[1671]
Relay Output [bin]
[1672]
Counter A
[1673]
Counter B
[1675]
Analog In X30/11
[1676]
Analog In X30/12
[1677]
Analog Out X30/8 [mA]
[1678]
Analog Out X45/1 [mA]
[1679]
Analog Out X45/3 [mA]
[1684]
Comm. Option STW
[1685]
FC Port CTW 1
[1690]
Alarm Word
[1691]
Alarm Word 2
[1692]
Warning Word
[1693]
Warning Word 2
[1694]
Ext. Status Word
[1695]
Ext. Status Word 2
[1696]
Maintenance Word
[1699]
Ext. Status Word 3
[1830]
Analog Input X42/1
[1831]
Analog Input X42/3
[1832]
Analog Input X42/5
[1833]
Analog Out X42/7 [V]
[1834]
Analog Out X42/9 [V]
[1835]
Analog Out X42/11 [V]
[1860]
Digital Input 2
[2827]
Discharge Temperature
8-45 BTM Transaction Command
Option:
[0]
Off
*
[1]
Start Transaction
[2]
Commit transaction
[3]
Clear error
8-46 BTM Transaction Status
Option:
[0]
Off
*
[1]
Transaction Started
[2]
Transaction Comitting
[3]
Transaction Timeout
[4]
Err. Non-existing Par.
MG16H202
Programming Guide
8-46 BTM Transaction Status
Function:
Option:
[5]
8-47 BTM Timeout
Range:
60 s
*
3.9.6 8-5* Digital/Bus
Parameters for configuring the control word merging.
NOTICE
These parameters are active only when
parameter 8-01 Control Site is set to [0] Digital and control
word.
8-50 Coasting Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-52 DC Brake Select
Option:
[0] Digital
Function:
input
[1] Bus
[2] Logic
AND
[3] Logic OR Activate a start command via the fieldbus/serial
Function:
Danfoss A/S © 05/2016 All rights reserved.
Err. Par. Out of Range
[0 - 360 s]
Function:
Select the trigger for the coasting function.
A digital input triggers the coasting function.
A serial communication port or the fieldbus
triggers the coasting function.
The fieldbus/serial communication port and a
digital input trigger the coasting function.
The fieldbus/serial communication port or a
digital input triggers the coasting function.
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
When parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM, only selection
[0] Digital input is available.
Activate a start command via a digital input.
Activate a start command via the serial communi-
cation port or fieldbus option.
Activate a start command via the fieldbus/serial
communication port, and also via 1 of the digital
inputs.
communication port, or via 1 of the digital inputs.
Function:
3
Function:
91
3

Advertisement

Table of Contents
loading

Table of Contents