How to Program
4.
Press [OK].
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
7.
Change parameter 14-22 Operation Mode back to
[0] Normal Operation.
NOTICE
Resets parameters selected in Personal Menu with
default factory setting.
Parameter 14-22 Operation Mode initializes all
except:
Parameter 14-50 RFI Filter.
Parameter 8-30 Protocol.
Parameter 8-31 Address.
Parameter 8-32 Baud Rate.
Parameter 8-35 Minimum Response Delay.
Parameter 8-36 Maximum Response Delay.
Parameter 8-37 Maximum Inter-Char Delay.
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's.
Parameter 15-20 Historic Log: Event to
parameter 15-22 Historic Log: Time.
Parameter 15-30 Alarm Log: Error Code to
parameter 15-32 Alarm Log: Time.
Manual initialization
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
Press [Status] - [Main Menu] - [OK] at
the same time while powering up (LCP
102, graphical display).
2b
Press [Menu] while powering up (LCP
101, numerical display).
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initializes all except:
•
Parameter 15-00 Operating hours.
•
Parameter 15-03 Power Up's.
•
Parameter 15-04 Over Temp's.
•
Parameter 15-05 Over Volt's.
MG16H202
Programming Guide
NOTICE
Manual initialization:
•
•
•
NOTICE
After initialization and power cycling, the display does
not show any information until after a couple of minutes.
Danfoss A/S © 05/2016 All rights reserved.
Resets serial communication.
Resets parameter 14-50 RFI Filter and fault log
settings.
Removes parameters selected in
parameter 25-00 Pack Controller.