Parameter Description
Ref.
(RPM)
High
ref.
value
P 5-53/
p 5-58
Low
ref.
value
P 5-52/
p 5-57
Low freq.
P 5-50/
P 5-55
Illustration 3.28 Pulse Input
5-50 Term. 29 Low Frequency
Range:
Function:
100
[0 - 110000
Enter the low frequency limit
Hz
Hz]
corresponding to the low motor shaft
*
speed (that is low reference value) in
parameter 5-52 Term. 29 Low Ref./Feedb.
Value. Refer to Illustration 3.28 in this
section.
5-51 Term. 29 High Frequency
Range:
Function:
100 Hz
[0 - 110000
Enter the high frequency limit
*
Hz]
corresponding to the high motor shaft
speed (that is high reference value) in
parameter 5-53 Term. 29 High Ref./Feedb.
Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0
[-999999.999 -
Enter the low reference value limit for the
*
999999.999]
motor shaft speed [RPM]. This is also the
lowest feedback value, see also
parameter 5-57 Term. 33 Low Ref./Feedb.
Value.
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100
[-999999.999 -
Enter the high reference value [RPM]
*
999999.999]
for the motor shaft speed and the high
feedback value, see also
parameter 5-58 Term. 33 High Ref./Feedb.
Value.
5-54 Pulse Filter Time Constant #29
Range:
Function:
NOTICE
100
[1 -
ms
1000 ms]
*
This parameter cannot be adjusted
while the motor is running.
MG16H202
Programming Guide
5-54 Pulse Filter Time Constant #29
Range:
High freq.
Input
5-55 Term. 33 Low Frequency
P 5-51/
(Hz)
P 5-56
Range:
100 Hz
5-56 Term. 33 High Frequency
Range:
100 Hz
5-57 Term. 33 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999]
5-58 Term. 33 High Ref./Feedb. Value
Range:
100
*
5-59 Pulse Filter Time Constant #33
Range:
100
ms
*
Danfoss A/S © 05/2016 All rights reserved.
Function:
Enter the pulse filter time constant. The
pulse filter dampens oscillations of the
feedback signal, which is an advantage if
there is a lot of noise in the system. A high
time constant value results in better
dampening, but also increases the time
delay through the filter.
Function:
[0 - 110000
Enter the low frequency corresponding
*
Hz]
to the low motor shaft speed (that is
low reference value) in
parameter 5-57 Term. 33 Low Ref./Feedb.
Value.
Function:
[0 - 110000
Enter the high frequency corresponding
*
Hz]
to the high motor shaft speed (that is
high reference value) in
parameter 5-58 Term. 33 High Ref./Feedb.
Value.
Function:
Enter the low reference value [RPM] for
the motor shaft speed. This is also the
low feedback value, see also
parameter 5-52 Term. 29 Low Ref./Feedb.
Value.
Function:
[-999999.999 -
Enter the high reference value [RPM]
999999.999]
for the motor shaft speed. See also
parameter 5-53 Term. 29 High Ref./
Feedb. Value.
Function:
NOTICE
[1 - 1000
ms]
This parameter cannot be adjusted
while the motor is running.
Enter the pulse filter time constant. The
low-pass filter reduces the influence, and
dampens oscillations on the feedback
signal from the control.
This is an advantage if there is a great
amount of noise in the system.