Parameter Description
[30]
Brake fault
The output is logic 1 when the brake IGBT
(IGBT)
is short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[35]
External
The external interlock function has been
Interlock
activated via 1 of the digital inputs.
[40]
Out of ref
range
[41]
Below
reference low
[42]
Above
reference high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if
timeout
[47]
Bus Ctrl 0 if
timeout
[55]
Pulse output
[60]
Comtor 0
See parameter group 13-1* Comparators. If
comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61]
Comtor 1
See parameter group 13-1* Comparators. If
comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62]
Comtor 2
See parameter group 13-1* Comparators. If
comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63]
Comtor 3
See parameter group 13-1* Comparators. If
comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64]
Comtor 4
See parameter group 13-1* Comparators. If
comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65]
Comtor 5
See parameter group 13-1* Comparators. If
comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See parameter group 13-4* Logic Rules. if
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group 13-4* Logic Rules. if
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
MG16H202
Programming Guide
[80]
SL Digital
Output A
[81]
SL Digital
Output B
[82]
SL Digital
Output C
[83]
SL Digital
Output D
[84]
SL Digital
Output E
[85]
SL Digital
Output F
[160] No alarm
[161] Running
reverse
[165] Local
reference
active
[166] Remote
reference
active
[167] Start
command
active
Danfoss A/S © 05/2016 All rights reserved.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [38] Set dig. out. A high is
executed. The input goes low whenever
the smart logic action [32] Set dig. out. A
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [39] Set dig. out. B high is
executed. The input goes low whenever
the smart logic action [33] Set dig. out. B
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [40] Set dig. out. C high is
executed. The input goes low whenever
the smart logic action [34] Set dig. out. C
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [41] Set dig. out. D high is
executed. The input goes low whenever
the smart logic action [35] Set dig. out. D
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [42] Set dig. out. E high is
executed. The input goes low whenever
the smart logic action [36] Set dig. out. E
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [43] Set dig. out. F high is
executed. The input goes low whenever
the smart logic action [37] Set dig. out. F
low is executed.
The output is high when no alarm is
present.
The output is high when the frequency
converter is running counter clockwise (the
logical product of the status bits running
AND reverse).
The output is high when
parameter 3-13 Reference Site=[2] Local or
when parameter 3-13 Reference Site=[0]
Linked to hand auto at the same time as
the LCP is in hand-on mode.
The output is high when
parameter 3-13 Reference Site = [1] Remote
or [0] Linked to hand/auto while the LCP is
in auto-on mode.
The output is high when there is an active
start command (that is via digital input,
bus connection, [Hand on] or [Auto on]),
and no stop command is active.
3