Parameter Description
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
[ 0 -
Enter the low current value. This reference
*
par. 6-23
signal should correspond to the low reference
mA]
feedback value, set in parameter 6-24 Terminal
54 Low Ref./Feedb. Value. Set the value at >2
mA to activate the live zero timeout function
in parameter 6-01 Live Zero Timeout Function.
6-23 Terminal 54 High Current
Range:
Function:
20 mA
[ par. 6-22
Enter the high current value
*
- 20 mA]
corresponding to the high reference
feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value.
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
-1
[-999999.999 -
Enter the analog input scaling value that
*
999999.999]
corresponds to the low voltage/low
current value set in
parameter 6-20 Terminal 54 Low Voltage
and parameter 6-22 Terminal 54 Low
Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Size
[-999999.999 -
Enter the analog input scaling
related
999999.999]
value that corresponds to the high
*
voltage/high current value set in
parameter 6-21 Terminal 54 High
Voltage and parameter 6-23 Terminal
54 High Current.
6-26 Terminal 54 Filter Time Constant
Range:
Function:
NOTICE
0.001 s
[0.001 - 10
*
s]
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 54. Increasing the value improves
dampening but also increases the time
delay through the filter.
6-27 Terminal 54 Live Zero
Option:
Function:
Disables the live zero-monitoring, for example if
the analog outputs are used as part of a
decentral I/O system (that is if these are used to
feed a building management system with data,
MG16H202
Programming Guide
6-27 Terminal 54 Live Zero
Option:
[0]
Disabled
[1]
Enabled
*
3.8.5 6-3* Analog Input 3 General Purpose
I/O MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) in VLT
101.
6-30 Terminal X30/11 Low Voltage
Range:
0.07 V
*
6-31 Terminal X30/11 High Voltage
Range:
10 V
*
10 V]
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999]
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
999999.999]
6-36 Term. X30/11 Filter Time Constant
Range:
0.001 s
*
Danfoss A/S © 05/2016 All rights reserved.
Function:
and not as part of any control functions related
to the frequency converter).
®
General Purpose I/OMCB
Function:
[ 0 - par.
Sets the analog input scaling value to
6-31 V]
correspond to the low reference feedback
value (set in parameter 6-34 Term. X30/11
Low Ref./Feedb. Value).
Function:
[ par. 6-30 -
Sets the analog input scaling value to
correspond to the high reference feedback
value (set in parameter 6-35 Term. X30/11
High Ref./Feedb. Value).
Function:
Sets the analog input scaling value to
correspond to the low voltage value (set
in parameter 6-30 Terminal X30/11 Low
Voltage).
Function:
Sets the analog input scaling value to
correspond to the high-voltage value
(set in parameter 6-31 Terminal X30/11
High Voltage).
Function:
NOTICE
[0.001 - 10
s]
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/11. A high value improves
dampening, but also increases the delay
through the filter.
3
3
81