5. Diagnosis CPV−CS02 (ABB CS31)
5.4

Fault treatment

5.4.1 Reaction of the CPV Direct to faults

5−12
Reaction to faults in the control system:
The CP valves and any electric outputs will be switched off
after 250 ms in the event of faults.
Note
Please note the following if the outputs are reset after
PLC stop, field bus interruption or fault:
Single−solenoid valves move to the basic position.
Double−solenoid valves remain in the current position.
Mid−position valves move to the mid−position (depend
ing on valve type: pressurized, exhausted or blocked).
Festo P.BE−CPV−DI02−E N en 0704NH