Diagnostics And Fault Clearance; Diagnostics Messages - Festo CPX-AP-A-8DO-M12-5P Operating Instructions Manual

Digital output module
Table of Contents

Advertisement

Diagnostics and fault clearance

ID
Parameter
20092
Operating time
20093
Hardware version
20099
Unlock test commands
1) ro = read only; rw = read write
Tab. 6: Parameter
9
Diagnostics and fault clearance
9.1

Diagnostics messages

ID hex (dec)
Message
01 | 01 | 010C
Output signal short-
(16843020)
circuit/overload
02 | 01 | 0016
Undervoltage in logic
(33619990)
supply PS 24 V DC
02 | 01 | 0017
Overvoltage in logic
(33619991)
supply PS 24 V DC
02 | 01 | 0105
Undervoltage in load
(33620229)
supply PL 24 V DC
Festo — CPX-AP-A-8DO-M12-5P — 2022-07
Instances Data type
1
1
1
Description
Short circuit/overload in output signal.
– Check connected load for correct function,
Remedy
in particular for current consumption.
– Check wiring.
Diagnos-
Error
tics
status
Undervoltage of the logic supply PS 24 V DC was
detected.
– Check logic supply PS.
Remedy
Diagnos-
Warning
tics
Error
status
Overvoltage in the logic supply PS 24 V DC has been
detected.
– Check logic supply PS.
Remedy
Diagnos-
Warning
tics
status
Undervoltage in the load supply PL 24 V DC has been
detected.
– Check load supply PL.
Remedy
Diagnos-
Error
tics
status
1
Access
)
UINT32
ro
UINT8
ro
UINT16
rw
Array
size
9

Advertisement

Table of Contents
loading

Table of Contents