Festo CPV-D102 Elektronics Manual page 84

With field bus direct connection
Table of Contents

Advertisement

3. Diagnosis CPV−DI02 (PROFIBUS−DP)
LED
Colour
BF
off
BF
red
flashes fast
BF
red
flashes slowly
(1−second
intervals)
BF
red
lights up
Tab. 3/4:
Fault diagnosis with the red LED BF
3−6
Fault diagnosis with the LED BF
The red LED BF (Bus fault") indicates the bus fault or bus
status.
Operating status
Normal operating status
PROFIBUS address not permitted
Field bus connection not OK.
Possible causes:
Station number not correct
(e.g. address assigned twice)
Field bus module switched off
or defective
Interrupted, short−circuited or
faulty field bus connection
Faulty PROFIBUS configuration
Hardware fault
Fault treatment
Correct address setting
·
(1; ...; 125)
Check the ...
address setting
·
field bus interface
·
field bus connection
·
the configuration of the master
·
and that in the CPV Direct and,
if necessary, carry out new
recognition (see section 1.2.4)
Servicing required
·
Festo P.BE−CPV−DI02−E N en 0704NH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpv-di02Profibud-dpCpv-cs02Abb cs31Profibus-dpCpv-di02 profibus-dp series ... Show all

Table of Contents