5. Diagnosis CPV−CS02 (ABB CS31)
LED
Colour
BF
off
BF
red
flashes fast
BF
red
flashes slowly
(1−second
intervals)
BF
red
lights up
Tab. 5/4:
Fault diagnosis with the red LED BF
5−6
Fault diagnosis with the LED BF
The red LED BF (Bus fault") indicates the bus fault or bus
status.
Operating status
Normal operating status
Station number not permitted
(. 60)
Field bus connection not OK.
Possible causes:
Station number not correct
(e.g. address assigned twice)
Field bus module switched off
or defective
Interrupted, short−circuited or
faulty field bus connection
Field bus configuration faulty
There is a hardware fault
Fault treatment
Correct the address setting on
·
the DIL switch
(see section 1.2.2)
Check the ...
address setting
·
field bus interface
·
field bus connection
·
the configuration of the master
·
and that in the CPV Direct and,
if necessary, carry out new
recognition (see section 1.2.4)
Servicing required
·
Festo P.BE−CPV−DI02−E N en 0704NH