Send Parametriziung Data - Festo CPV-D102 Elektronics Manual

With field bus direct connection
Table of Contents

Advertisement

A. Technical appendix
A.2.2 Send parametriziung data
Set_Prm
Octet 1: Station status
Bit
Meaning
0
1
2
3
WD_On
4
Freeze_Req
5
Sync_Req
6
Unlock_Req
7
Lock_Req
Tab. A/1:
Octet 1: Station status
Festo P.BE−CPV−DI02−EN en 0704NH
The parametrizing data are transferred from the DP master
to the valve terminal with the function Set_Prm.
Explanation
reserved
Response monitoring of the CPI system ON/OFF:
0 = OFF
1 = ON
0 = FREEZE mode not requested by the master
1 = FREEZE mode set by the master
0 = SYNC mode not requested by the master
1 = SYNC mode set by the master
Bit 7
Bit 6
Explanation
0
0
min T
SDR
0
1
CPI system released for other masters
1
0
CPI system blocked for other masters
1
1
CPI system released for other masters
+ slave parameters may be overwritten
A−7