Diagnostics and fault clearance
ID
Parameter
20014
Input debounce time
–
0: 0.1 ms
–
1: 3.0 ms (factory setting)
–
2: 10 ms
–
3: 20 ms
20085
Measured value temperature AP-ASIC [°C]
20087
Current measured value of logic supply PS
[mV]
20088
Current measured value of load supply PL
[mV]
20093
Hardware version
1) ro = read only; rw = read write
Tab. 10 Parameter
10
Diagnostics and fault clearance
10.1
Diagnostic messages
ID hex (dec)
Message
01
01
010B
Short circuit/overload
|
|
(16843019)
in sensor supply
02
01
0016
Undervoltage in logic
|
|
(33619990)
supply PS 24 V DC
02
01
0017
Overvoltage in logic
|
|
(33619991)
supply PS 24 V DC
Tab. 11 Diagnostic messages
Festo — CPX-AP-I-8DI-M12-5P — 2019-06
Instance-
s
4
1
1
1
1
Description
A short-circuit/overload of the sensor supply was detec-
ted.
Remedy
–
Check connected load for correct function,
in particular for power consumption.
–
Check sensor and wiring.
Diagnost-
Error
ic status
Undervoltage of the logic supply PS 24 V DC was detec-
ted.
Remedy
–
Check logic supply PS.
Diagnost-
Warning
ic status
Error
Overvoltage in the logic supply PS 24 V DC detected.
Remedy
–
Check logic supply PS.
Diagnost-
Error
ic status
Data
Access
1)
type
UINT8
rw
INT16
ro
UINT16
ro
UINT16
ro
UINT8
ro
Arraysize
–
–
–
–
–