Bus Termination With Termination Resistors (Cpv−Di02); Installation Cpv−Di02 And Cpv−Cs02 - Festo CPV-D102 Elektronics Manual

With field bus direct connection
Table of Contents

Advertisement

1. Installation CPV−DI02 and CPV−CS02
1.4
Bus termination with termination resistors (CPV−DI02)
1−24
Note
If the valve terminal is at the beginning or the end of the
field bus system, a bus termination will be required.
Fit a bus termination to both ends of a bus segment.
·
Recommendation:
Use the ready−to−use field bus plugs from Festo for the bus
termination. A suitable resistor network is incorporated in the
housing of this plug (see Fig. 1/7).
Receive/send data P
(data cable B)
Receive/send data N
(data cable A)
Fig. 1/7: Circuit diagram for bus termination network
(switch in Festo field bus plug set to ON)
(PROFIBUS−DP: for cable type A as per EN 50170)
Pin 6: Supply voltage
120 nH
Pin 3
120 nH
Pin 8
Pin 5: Data reference potential
Festo P.BE−CPV−DI02−EN en 0704NH
390
220
390