Diagnostics And Fault Clearance; Diagnostics Messages - Festo CPX-AP-A-12DI4DO-M12-5P Operating Instructions Manual

Digital input/output module
Table of Contents

Advertisement

Diagnostics and fault clearance

ID
Parameter
20022
Configuration of voltage monitoring load
supply PL
– 0: load voltage monitoring inactive
– 1: load voltage monitoring active, with
suppression of diagnostics at switch-off
(factory setting)
– 2: load voltage monitoring active
20052
Response in error status (communication
malfunction)
– 0: reset outputs (factory setting)
– 1: maintain status
20085
Measured value of temperature AP-ASIC [°C] 1
20087
Current measured value of logic supply (PS) 1
20088
Current measured value of load supply (PL)
20093
Hardware version
1) ro = read only; rw = read write
Tab. 8: Parameter
9
Diagnostics and fault clearance
9.1

Diagnostics messages

The following table contains the diagnostic messages of the module.
ID hex (dec)
Message
01 | 01 | 010B
Short circuit / Over-
(16843019)
load sensor supply
01 | 01 | 010C
Short circuit / Over-
(16843020)
load output signal
10
Instances Data type
1
1
1
1
Description
A short circuit/overload of the sensor supply was detected
– Check the connected sensors for proper
Remedy
function, especially current consumption.
– Check sensor cable.
Diag-
Error
nostic
status
Connected digital output load exceeds allowed power con-
sumption.
– Check the connected load for proper func-
Remedy
tion, especially current consumption.
– Check cable.
– The output must be reset after the fault is
resolved.
Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07
1
Access
)
UINT8
rw
UINT8
rw
INT16
ro
UINT16
ro
UINT16
ro
UINT8
ro
Array
size

Advertisement

Table of Contents
loading

Table of Contents