Cleaning; Malfunctions; Fault Clearance; Disassembly - Festo MS6-SV D-10V24 Series Instructions Manual

Soft start/quick exhaust valve
Hide thumbs Also See for MS6-SV D-10V24 Series:
Table of Contents

Advertisement

Malfunctions

10.2

Cleaning

1. Switch off energy sources:
Operating voltage
Compressed air
2. Clean the outside of the product as required. Approved cleaning agents are soap solutions (max.
+50 °C), petroleum ether and all non-abrasive cleaning agents.
11
Malfunctions
11.1

Fault clearance

Check compressed air supply
Check power supply
Check installation of the signal lines
Start device è 8 Commissioning.
Implement possible remedies è Tab. 8 Fault clearance.
If the fault occurs again: contact Festo service è www.festo.com.
Malfunction
Product does not
switch
Pressure p1 collapses
briefly at every switch-
ing operation
Tab. 8 Fault clearance
12

Disassembly

1. Switch off energy sources
Operating voltage
Compressed air
2. Separate the applicable connections from the product.
Festo — MS6-SV-...-D-10V24 — 2019-05b
Possible cause
Power supply is insufficient
Pressure supply interrupted
Malfunction due to electrical or elec-
tromagnetic effects (EMC measures
not complied with).
The cross-section of the MS6-SV-D
pressure supply is too small.
Remedy
Provide sufficient power supply.
Restore compressed air supply.
Note maximum length of the sig-
nal lines.
Run the control and power lines
separately.
Use screened cables.
Provide low-impedance paths to
earth.
Tighten flow control screw a
little.
Attach reservoir in front of inlet
p1.
Modify the compressed air sup-
ply, e. g. increase cross-section
of the power supply cable.