Fault Clearance - Festo MS6-SV E-10V24 Series Instructions Manual

Soft start/quick exhaust valve
Hide thumbs Also See for MS6-SV E-10V24 Series:
Table of Contents

Advertisement

Malfunctions
Fig. 18 Example of error code
After 4 short flash pulses of the Power LED 1, there are 6 long flash pulses of the Error LED 2. This
indicates error code 6 (pneumatic fault). A pneumatic fault occurs, for example, if the operating pres-
sure is below the required minimum pressure or there is no pressure at all.
11.2

Fault clearance

Check compressed air supply
Check power supply
Check installation of the signal lines
Start device .
If the fault occurs again: contact Festo service è www.festo.com.
Malfunc-
Possible cause
tion/
error code
2
Bouncing on the enable signals
5
Power supply is insufficient
Power unit is not correctly dimensioned;
voltage collapses
6
Pressure supply was interrupted
8
Enable signals outside the specification
Multi-pin plug socket NECA or cable is
defective
Additional
PLC emits test pulses that are offset to the
Error codes
enable signals
Malfunction due to electrical or electro-
magnetic effects (EMC information not in
compliance)
Festo — MS6-SV-...-E-10V24 — 2019-10d
Remedy
Make sure that only debounced con-
tacts are used (e.g. for protective
guards or doors).
provide sufficient power supply.
use a sufficiently dimensioned power
unit.
Restore compressed air supply.
Comply with specification .
NECACheck multi-pin plug socket or
wiring and replace if defective.
Switch off test pulses.
Use MP5 plug connector.
note maximum length of the signal
lines.
Connect earthing correctly.
maintain minimum wall distance.
Do not install cables behind the
product.