Malfunctions
LED green
LED red
Tab. 32 Status indicator
Diagnostics via status word
The status word facilitates the diagnosis of faults and their origin. Structure of the status word
è Tab. 20 Meanings of the bits in the status word.
Bit
Bit 0
Bit 3
Bit 4
Meaning
Tab. 33 Frequent bit combinations in the status word
9.2
Fault clearance
9.2.1
Resetting the active error bit
If an error occurs, the error bit, bit 3 in the status word, is activated. This must be reset manually. To
reset this, a state change of 0 à 1 must take place in the control word at bit 3. To ensure continued
operation, the control word must be reset to its original state.
1. Reset control word.
–
Via ASCII telegram: WU16: I1S0V0
–
Using Modbus TCP: 0000 0000 0019 00 17 0000 0007 0000 0007 0E 01 02
0001 00 00 0000 0000 0000 0000
2. Set bit 3 in the control word.
–
Via ASCII telegram: WU16: I1S0V8
–
Using Modbus TCP: 0000 0000 0019 00 17 0000 0007 0000 0007 0E 01 02
0001 00 00 0000 0000 0000 0008
9.2.2
System faults
In the event of a system fault, all selected valves are deactivated in the status word. The red LED
flashes and error bit 3 in the status word becomes active.
26
Description
Operating system error
Bootloader mode
This mode shows that a firmware update has failed.
Firmware update is being run
Bit combination 1
1
1
0
Error in the operating phase and
1 connected valve error-free
³
Bit combination 2
0
1
0
No operating phase and faults
on one or more valves
Festo — VAEM-V-S8EPRS2 — 2020-07