3. Diagnosis PROFIBUS-DP
3.4

Error treatment

Festo P.BE-CP-DI01-EN en 0007a
With the following faults, the reaction of the CP system de-
pends on the configured reaction of the master module:
telegram failure
master has stopped
interruption in bus cable.
If the setting or configuration is successful, all the outputs
(valves and electric outputs) will be switched off or maintain
their status.
Warning
S Make sure that valves and outputs are reset when the
faults mentioned occur.
A dangerous situation can arise if the valves and outputs
are not reset.
Please note
If the outputs are reset after PLC stop, field bus interrup-
tion or fault, please observe the following:
– single-solenoid valves move to the basic position
– double-solenoid valves remain in the current position
– mid-position valves move to the mid-position (depend-
ing on valve type): pressurized, exhausted or blocked).